Class PX is the definition in IEC 60044-1 for the quasi-transient CT formerly covered by Class X of BS-3938, commonly used with unit protection schemes. These are Protection CTs used for Earth fault protection. Knee point voltage is an important parameter for these type of CTs. Shaikh
Class X CTs are special CTs used mainly in balanced protection systems (including restricted earth fault) where the system is sensitively dependent on CT accuracy. Further to the general CT specifications, the manufacturer needs to know: • Vkp - Voltage knee point • Io - Maximum magnetising current at Vkp • Rs - Maximum resistance of the secondary winding